(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Instead, please kindly use other browsers like Google Chrome, Microsoft Edge or Mozilla Firefox.

  • Scheduled Maintenance Notice: This site will be unavailable due to scheduled maintenance from 9:00 24/11/2024 to 7:00 (SGT) 25/11/2024. We apologize for the inconvenience.
  • Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information.

L Series CC-Link/LT Master Unit (Part Numbers)

Part Number

Configured Part Number is shown.

LJ61CL12

L Series CC-Link/LT Master Unit Specifications

L Series CC-Link/LT Master Unit image

L Series CC-Link/LT Master Unit image

Performance Specifications

Control Specifications
Point Modes4‑point mode / 8‑point mode / 16‑point mode
Maximum Link Points ( ) Is For When The Same Input/Output Address Is Used4‑Point Mode256 points (512 points)
8‑Point Mode512 points (1,024 points)
16‑Point Mode1,024 points (2,048 points)
Link Points Per 1 Station ( ) Is For When The Same Input/Output Address Is Used4‑Point Mode4 points (8 points)
8‑Point Mode8 points (16 points)
16‑Point Mode16 points (32 points)
Link Scan Time32 Stations Connected4‑Point ModeNumber of points: 128
2.5 Mbps: 0.7 ms
625 kbps: 2.2 ms
156 kbps: 8.0 ms
8‑Point ModeNumber of points: 256
2.5 Mbps: 0.8 ms
625 kbps: 2.7 ms
156 kbps: 10.0 ms
16‑Point ModeNumber of points: 512
2.5 Mbps: 1.0 ms
625 kbps: 3.8 ms
156 kbps: 14.1 ms
64 Stations Connected4‑Point ModeNumber of points: 256
2.5 Mbps: 1.2 ms
625 kbps: 4.3 ms
156 kbps: 15.6 ms
8‑Point ModeNumber of points: 512
2.5 Mbps: 1.5 ms
625 kbps: 5.4 ms
156 kbps: 20.0 ms
16‑Point ModeNumber of points: 1,024
2.5 Mbps: 2.0 ms
625 kbps: 7.4 ms
156 kbps: 27.8 ms
Communication Specifications
Transmission Speed2.5 Mbps / 625 kbps / 156 kbps
Communication MethodBITR method (broadcastpolling + interval timed response)
Transmission Path TypeT-Branch Method
Error Control MethodCRC
Number Of Connected Units64 devices
Remote Station Number1 to 64
Master Station Connection PositionConnected to the End of the Main Line
Communication CableDedicated flat cable (0.75 mm2 × 4)
VCTF cable
Flexible cable
Unit Specification
External Power SupplyVoltage20.4 to 28.8 V DC
Current0.03 A
Current At Startup0.07 A
Number Of Occupied Inputs/Outputs16/32/48/64/128/256/512/1,024 points (I/O assignment: intelligent)
5 V DC Internal Current Consumption0.16 A
External DimensionsHeight (H)90 mm
Width (W)28.5 mm
Depth (D)95 mm
Mass0.12 kg
Part Number
LJ61CL12
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to Ship

-

1 Piece(s) Quote

Loading...

  1. 1
 

Basic Information

Communication Interface (Transmission Standard) Other Representative Standard CE / UL / CUL

Please check the type/dimensions/specifications of the part LJ61CL12 in the L Series CC-Link/LT Master Unit series.

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)