Solid State/Timer H3Y

Solid State/Timer H3Y
  • On Sale Till 31/03/2025

Ultra-small timer for use in sequence control incorporating a dedicated IC.
[Features]
· Highly accurate with a repeat error of ±1% (including first time value).
· Recovery time including recovery during operation is 100 ms or less.
· Time is easily set using the large dial that works with either straight-slot or Phillips-head screwdrivers.
· Semi-multi power supply voltages.
· Standard product complies with UL and CSA standards.
· EN61812-1 compatible, conforms to the CE mark.
[Applications]
· Many facilities require timer functions, and this can be used anywhere on the line.

PDF

Japanese Only

Product features

H3Y Solid-State Timer: Related images

External appearance of H3Y

Maximum scale timeTime Setting Range
0.5 s0.04 s to 0.5 s
1s0.1 s to 1.0 s
5 s0.2 s to 5.0 s
10 s0.5s to 10 s
30 s1.0 s to 30 s
60 s2.0 s to 60 s
120 s5.0 s to 120 s
3 min0.1 min to 3 min
5 min0.2 min to 5 min
10 min0.5 min to 10 min
30 min1.0 min to 30 min
60 min2.0 min to 60 min
3 h0.1 h to 3 h

Rating

Model numberSeries H3Y-2 (-0)Series H3Y-4 (-0)
Power supply voltage *6・ 100 to 120 V AC, 50/60 Hz, 200 to 230 V AC, 50/60 Hz
・ 24 V AC, 50/60 Hz *1
・DC12V ・DC24V ・DC48V ・DC100 to 110 V ・DC125V *2, *3
Allowable voltage fluctuation range85 to 110% of power supply voltage (However, 90 to 110% of power supply voltage only for 12 V DC specifications) *4
Power consumptionAC100 to 120 V1.5 VA (at 120 V AC)
AC200 to 230 V1.8 VA (at 230 V AC)
AC24V1.5 VA (at 24 V AC)
DC12V0.9 W (at 12 V DC)
DC24V0.9 W (at 24 V DC)
DC48V1.0 W (at 48 V DC)
DC100 to 110 V1.3 W (at 110 V DC)
DC125V1.3 W (at 125 V DC)
Reset voltage10% or more of power supply voltage *5
Control output250 V AC 5 A, resistant load (cosø = 1)
Minimum compatible load 5 V DC 1 mA (P level, reference value)
Contact Materials: Ag
250 V AC 3 A, resistant load (cosø = 1)
Minimum compatible load 1 V DC 1 mA (P level, reference value)
Contact Materials: Au clad + Ag alloy
Operating Ambient Temperature-10 to +50℃ (However, do not freeze)
Storage temperature-25 to +65℃ (However, do not freeze)
Operating ambient humidity35 to 85%

*1. The inverter output should not be used as a power supply.
*2. Single-phase, full-wave-rectified power supplies can be used.
*3. Only the H3Y-2 and H3Y-2-0 types include 12 V DC models.
* 4. When using continuously at an operating ambient temperature of 50°C, 90 to 110% of the power supply voltage (95 to 110% for 12 V DC) should be used.
* 5. For reliable reset, 100 to 120 V AC should be set to 10 V AC, 200 to 230 V AC should be set to 20 V AC, and 100 to 110 V DC should be set to 10 V DC or less.
*6. A diode to prevent reverse voltages is provided only on models with a DC power supply voltage.

Performance

Model numberSeries H3Y-2 (-0)Series H3Y-4 (-0)
Accuracy of operating time±1% or less (at maximum scale time) *1
Setting error±10% ±50 ms max. (at maximum scale time)
Reset time0.1 s max. (including halfway reset)
Influence of voltage±2% or less (at maximum scale time) *1
Influence of temperature±2% or less (at maximum scale time) *1
Insulation resistance100 MΩ or more (Measured at 500 V DC insulation resistance tester)
Withstand voltage2,000 V AC, 50/60 Hz for 1 min (Between current-carrying terminals and exposed non-current-carrying metal parts, except for the terminal thread section)
2,000 V AC, 50/60 Hz for 1 min (Between operating power supply circuit and control output)
2,000 V AC, 50/60 Hz for 1 min (Between different pole contacts; 2-pole model)
1,500 V AC 50/60 Hz 1 min (Between different pole contacts; 4-pole model)
1,000 V AC 50/60 Hz 1 min (Between non-continuous contacts)
Impulse voltageBetween power supply terminals: 3 kV, 1 kV for 12 V DC, 24 V DC, 48 V DC
Between exposed non-current-carrying metal parts: 4.5 kV, 1.5 kV for 12 V DC, 24 V DC, 48 V DC
Noise immunitySquare-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) ±1.5 kV
Static immunityMalfunction: 4 kV, Destruction: 8 kV
VibrationDestruction10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
Malfunction10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
ImpactDestruction1,000 m/s^2 for 3 times each in 6 directions *2
Malfunction100 m/s^2 for 3 times each in 6 directions
LifespanMechanical10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical2-pole: 500,000 operations min. (250 V AC 5 A, resistant load at 1,800 operations/h) (At normal temperature)
4-pole: 200,000 operations min. (250 V AC 3 A, resistant load at 1,800 operations/h) (At normal temperature)
Protective structureIP40
WeightApprox. 50 g

*1. ±10 ms is added to the above value for the 0.5 s range model.
*2. The destructive impact resistance test was performed on the timer.

  • *See the catalog for any types or part numbers other than those detailed above.
Part Number
H3Y-2 AC100-120 3M
H3Y-2 AC200-230 3M
H3Y-2 DC12 3M
H3Y-2 DC24 3M
H3Y-4 AC100-120 3M
H3Y-4 AC200-230 3M
H3Y-4 DC24 3M
H3Y-4 DC100-110 3M
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSType Time specifications
(s)
Power Supply Voltage Rated power supply voltage
(V)
Contact Configuration Terminal shape

SGD 54.40

SGD 10.88

1 Piece(s) Same day -Timer0.1m to 3mAC-dedicatedAC100 to 120Time Limit 2cPlug-in terminal

SGD 54.40

SGD 10.88

1 Piece(s) Same day -Timer0.1m to 3mAC-dedicatedAC200 to 230Time Limit 2cPlug-in terminal

SGD 53.97

1 Piece(s) 4 Day(s) or more -Timer0.1m to 3mDedicated to DCDC12Time Limit 2cPlug-in terminal

SGD 51.67

SGD 10.33

1 Piece(s) Same day -Timer0.1m to 3mDedicated to DCDC24Time Limit 2cPlug-in terminal

SGD 58.47

SGD 11.69

1 Piece(s) Same day -Timer0.1m to 3mAC-dedicatedAC100 to 120Time Limit 4cPlug-in terminal

SGD 58.47

1 Piece(s) 4 Day(s) or more -Timer0.1m to 3mAC-dedicatedAC200 to 230Time Limit 4cPlug-in terminal

SGD 58.20

1 Piece(s) 4 Day(s) or more -Timer0.1m to 3mDedicated to DCDC24Time Limit 4cPlug-in terminal

SGD 48.42

1 Piece(s) 4 Day(s) or more -Timer0.1m to 3mDedicated to DCDC100 to 110Time Limit 4cPlug-in terminal

Loading...

  1. 1
 

Basic Information

Display method Analog Output Method Relay Representative Standard CE / UL / CCC / CSA
Dimension vertical(mm) 52.6 Dimension width(mm) 28 Dimension depth(mm) 21.5
Time ranges = N 1 range

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211