MELSEC-QS Series CC-Link Safety Input/Output (QS0J65BTS2-4T)

MELSEC-QS Series CC-Link Safety Input/Output QS0J65BTS2-4T

- CC-Link Safety Remote I/O modules, Terminal block type, MELSEC-QS Series from MITSUBISHI.
- 2 terminal block types available, Screw terminal block type and Spring clamp terminal block type.
- The system complying with Category 3 or Category 4 of EN 954-1 can be configured by the combination of wiring and parameters.
- Rated input voltage: 24 V DC
- Ingress protection level: IP2X
- The remote I/O module which has obtained the highest safety level applicable to programmable controllers, and the safety-related system with high security can be configured.

PDF

Part Number

Configured Part Number is shown.

QS0J65BTS2-4T

MELSEC-QS Series CC-Link Safety, Safe Input/Output Specifications

QS0J65BTB2-12DT-K

QS0J65BTB2-12DT-K image

QS0J65BTB2-12DT-K image

QS0J65BTB2-12DT-K Performance Specifications

Input Specifications
Number of Inputs8 (for duplexing input)
16 (for single output)
Rated Input Voltage24 V DC (ripple ratio within 5%) (allowable voltage range from 19.2 to 28.8 V DC)
Rated Input CurrentApprox. 4.6 mA
Maximum Number of Simultaneous Input Points100%
ON Voltage / ON Current15 V DC or more / 2 mA or more
OFF Voltage / OFF Current5 V DC or less / 0.5 mA or less
Input ResistanceApprox. 5.6 kΩ
Input FormatDC input (negative common type)
Input Response TimeOFF > ON0.4 ms or less (24 V DC)
ON > OFF0.4 ms or less (24 V DC)
Safety Remote Station Input Response Time11.2 ms or less + denoising filter time (1 ms, 5 ms, 10 ms, 20 ms, 50 ms)
Input Common Method16 points 1 common (terminal block model, 2-wire type)
Input Insulation MethodOpto-isolator insulation
Output Specifications
Number of Outputs4 points (when selecting source + sink type)
2 points (when selecting source + source type)
Rated Load Voltage24 V DC
Operating Load Voltage Range19.2 to 28.8 V DC (Ripple ratio within 5%)
Maximum Load Current0.5 A / 1 point
Maximum Inrush Current1.0 A, 10 ms or less
Leakage Current When OFF0.5 mA or less
Maximum Voltage Drop When ON1.0 V DC or less
Protection FunctionOutput Overload Protection Function
Output FormatSource + sink type
Source + source type
Output Response TimeOFF > ON0.4 ms or less (24 V DC)
ON > OFF0.4 ms or less (24 V DC)
Safety Remote Station Output Response TimeOFF > ON11.2 ms or less
ON > OFF10.4 ms or less
Surge SuppressorZener diode
Output Common Method4 points 1 common (terminal block model, 2-wire type)
Common CurrentMaximum 4 A (total of input and output)
Output Insulation MethodOpto-isolator insulation
Common Specifications
Dielectric StrengthBetween all DC external terminals as a whole and the earth: 500 V AC for 1 minute
Insulation ResistanceBetween all DC external terminals as a whole and the earth: 10 MΩ or more at 500 V DC on an ohmmeter
Protection GradeIP2X
Station TypeSafety remote I/O station
Number of Occupied Stations1
Number of Accesses to the Non-volatile Memory Inside the Unit1012
Safety Remote Station Refresh Response Process Time9.6 ms
External Power SupplyVoltage19.2 to 28.8 V DC (Ripple ratio within 5%)
Current60 mA (for 24 V DC and with all points ON, not including external load current)
Protection FunctionExternal supply power overvoltage protection function, external supply power overcurrent protection function
Fuse8 A (non-replaceable)
Unit Power SupplyVoltage19.2 to 28.8 V DC (Ripple ratio within 5%)
Current140 mA or less (24 V DC, with all points are ON)
Protection FunctionUnit power supply overvoltage protection function, unit power supply overcurrent protection function
Fuse0.8 A (non-replaceable)
Allowable Momentary Power Loss TimeWithin 10 ms
External Wiring Connection MethodCommunication part, unit power supply part: 7-point 2-piece terminal block (M3 screw)
Input/output power supply, input/output part: 18-point 2-piece terminal block (M3 screw) x 3
Weight0.71 kg

QS0J65BTB2-12DT-K General Specifications

Ambient Operating Temperature0 to 55°C
Ambient Storage Temperature-40 to 75°C
Ambient Operating Humidity5 to 95% RH, assuming non-condensing
Ambient Storage Humidity5 to 95% RH, assuming non-condensing
Vibration ResistanceJIS B 3502, IEC 61131-2 CompatibleUnder Intermittent VibrationFrequency: 5 to 8.4 Hz, Single amplitude: 3.5 mm
Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m/s2
Sweeps: 10 sweeps in each direction of X, Y and Z
Under Continuous VibrationFrequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm
Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m/s2
Impact ResistantJIS B 3502, IEC 61131-2 compatible
(147 m/s2,for a duration of 11 ms, 3 times in 3 directions of X, Y and Z with a half-sine pulse)
Operating AtmosphereNo Corrosive Gas
Operating Altitude0 to 2,000 m
Installation LocationInside the control panel
Overvoltage CategoryII or lower
Pollution Degree2 or less
Equipment ClassClass III
Part Number
QS0J65BTS2-4T
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipType of unit

-

1 Piece(s) Quote CC-Link Safety Safe Output

Loading...

  1. 1
 

Basic Information

Representative Standard CE / UL

Please check the type/dimensions/specifications of the part QS0J65BTS2-4T in the MELSEC-QS Series CC-Link Safety Input/Output series.

Similar Part Numbers

Part Number
QS0J65BTB2-12DT
QS0J65BTS2-8D
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipType of unit

-

1 Piece(s) Quote CC-Link Safety Safe Input/Output

-

1 Piece(s) Quote CC-Link Safety Safe Input

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)