(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Instead, please kindly use other browsers like Google Chrome, Microsoft Edge or Mozilla Firefox.

  • Scheduled Maintenance Notice: This site will be unavailable due to scheduled maintenance from 9:00 24/11/2024 to 7:00 (SGT) 25/11/2024. We apologize for the inconvenience.
  • Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information.

NAC Series Single-Phase Noise Filter (General-Purpose / Single-Stage Filter / Low-Frequency Attenuation) (NAC-30-472-D)

NAC Series Single-Phase Noise Filter (General-Purpose / Single-Stage Filter / Low-Frequency Attenuation) NAC-30-472-D
  • Volume Discount

Noise terminal noise filter for voltage suppression.
[Features]
·150 kHz to 1 MHz high attenuation type.
·ø1 noise filter.
·Single-phase 250 V.
·Lineup from 4 to 30 A. (4 A/6 A/10 A/16 A/20 A/30 A)
·It uses a quick and easy push-down terminal block.
·With screw fall prevention function.
·It has mounting compatibility with NAC, NAH, NAM, NMP and can be used properly according to the application.
·Ground capacitor that can be selected according to the application.
·DIN rail mounting type is available as an option.
[Applications]
·Ideal for using multiple switched-mode power supplies, single-phase inverters, etc.

(i)Caution

  • The delivery date is unstable due to the difficulty in obtaining materials, components, etc.
    Sales of products currently in stock may be temporarily suspended in the future depending on their availability.
    Products for which orders have been suspended are not expected to be restocked anytime soon.
  • Those with "-R6" at the end of the part number are MISUMI original models.
    If you want a product that compatible with the revised RoHS directive, please search by the model number with "-R6" removed with the part number search.

PDF

Part Number

Configured Part Number is shown.

NAC-30-472-D

INDEX

Features of NAC series

NAC series

NAC series

150 kHz to 1 MHz high attenuation type
Single-phase 250 V
It uses a quick and easy push-down terminal block (With screw fall prevention function)

Ordering information

Ordering information

Ground capacitor code

CodeLeakage current
Input 125/250 V 60 Hz
Capacitor capacity
(Nominal value)
68175.5 µA / 150 µA max680 pF
1020.13 mA / 0.25 mA max1,000 pF
2220.25 mA / 0.5 mA max2,200 pF
3320.38 mA / 0.75 mA max3,300 pF
4720.5 mA / 1.0 mA max4,700 pF

1 Series name.
2 Rated current.
3 Ground capacitor code.

  • * The attenuation characteristic differs depending on the ground capacitor code.

4 Option D: DIN rail mounting type.

  • * The external shape differs when the option is set. Please refer to the drawing.

Product specifications

ItemNAC-04-472NAC-06-472 NAC-10-472NAC-16-472NAC-20-472 NAC-30-472
Rated Voltage〔V〕AC 1⌀250 / DC250
Rated current〔A〕4610162030
Test voltage (Between terminals and mounting plates)2,500 V AC (cutoff current = 20 mA), 1-minute, normal temperature normal humidity
Insulation resistance (Between terminals and mounting plates)500 V DC 100 MΩ min normal temperature normal humidity
Leakage current 125/250 V 60 Hz0.5 mA / 1.0 mA max
Voltage drop1.0 V max
Safety standard certified temperature-25 to +85°C (Refer to the derating characteristics)
Operating Temperature-40 to +85°C (Refer to the derating characteristics)
Operating Humidity20 to 95% RH (No condensation)
Storage temperature/humidity-40 to +85°C, 20 to 95%RH (No condensation)
Vibration10 to 55 Hz, 19.6 m/s^2 (2 G), period 3 minutes X, Y, Z direction 1 hour each
Impact196.1 m/s^2 (20 G) 11 ms X, Y, Z direction 1 time each
Safety StandardUL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (Except for DC input)
External dimensions (excluding protrusions) / weight53 × 41 × 92 mm (W × H × D) / 300 g max (Option: for -D, refer to the drawing)

Circuit Configuration

Circuit Configuration

Derating characteristics

Derating characteristics

Drawing

Since this product uses a push-down terminal block, it is shipped in the following conditions.
1 Terminal block cover is stored.
2 Terminal block screw is retained on the upper side.

Standard type

Standard type

DIN rail mounting type

DIN rail mounting type

  • * Tolerance: ±1
  • * Weight: 300 g max
  • * Mounting plate material: Steel (surface treatment: nickel plating) t = 1.0
  • * Case material: PBT
  • * Unit mm
  • * Terminal block tightening torque M4: 1.6 N⋅m (16.9 kgf⋅cm) max

Precautions for mounting DIN rail

Grounding through a DIN rail may not provide the proper noise attenuation effect.
Grounding should be done by connecting to the protective ground terminal (PE) of the noise filter main body.
There are 2 protective ground terminals, but you can use it even by connecting only one of them.

Precautions for mounting DIN rail

Characteristic data (Representative example)

NAC-06-472

Attenuation characteristic (Static characteristics)

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs

Pulse attenuation characteristics pulse width 1 µs

NAC-10-472

Attenuation characteristic (Static characteristics)

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs

Pulse attenuation characteristics pulse width 1 µs

NAC-16-472

Attenuation characteristic (Static characteristics)

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs

Pulse attenuation characteristics pulse width 1 µs

NAC-20-472

Attenuation characteristic (Static characteristics)

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs

Pulse attenuation characteristics pulse width 1 µs

NAC-30-472

Attenuation characteristic (Static characteristics)

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs

Pulse attenuation characteristics pulse width 1 µs

Part Number
NAC-30-472-D
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSRated Current
(A)
Mounting Method H
(mm)
Leak current value
(mA max)

SGD 34.74

1 Piece(s)Available 4 Day(s) or more 1030DIN Rail481(250V60Hz)

Loading...

  1. 1
 

Basic Information

Input Type Single-Phase Wiring Method Screw Fastening Safety standards UL / CUL / CSA
D(mm) 92 W(mm) 53 Representative standards (VDE) Corresponds To
Representative standards (ENEC) Corresponding (excluding time of DC input) 150 kHz to 1 MHz, high attenuation Corresponds To

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)