MELSEC-F Analog Input

MELSEC-F Analog Input

Analog input/output unit.
[Features]
· Analog input board: Can be used for both voltage input and current input. The sequencer is built in, so it doesn't need space for mounting.
· Analog input block / analog input adapter: Each channel can be designated either voltage or current input.
· Analog input adapter: Programless (no dedicated commands), so forwarding of data is possible.
[Applications]
· Convenient for conversion of analog input signal to digital values, and for conversion of digital values to analog output signal.

PDF

FX3G-2AD-BD

MELSEC-F analog input: related images

Product image

  • A two-channel analog input board that can be fitted inside the FX3S or FX3G (V1.10 or later) sequencer.
  • The sequencer is built in, so doesn't need space for mounting.
  • Can be used for both voltage input and current input.

Specifications

Analog InputAnalog Input RangeVoltage Input0 V To 10 V DC(Input Resistance 198.7 kΩ)
Current Input4 mA To 20 mA DC (Input Resistance 250 Ω)
Number Of Input Channels2 Channel
Absolute Maximum InputVoltage Input-0.5 V, +15 V
Current Input-2 mA, +30 mA
Input Characteristics· Voltage Input And Current Input Can Be Used Together.
· Input Characteristics Cannot Be Adjusted.
Digital OutputVoltage Input12-bit Binary
Current Input11-bit Binary
ResolutionVoltage Input2.5 mV (10 V × 1/4,000)
Current Input8 μA (16 mA × 1/2,000)
Overall PrecisionVoltage InputAmbient Temperature 25°C ±5°C: For Full-scale 10 V ±0.5% (±50 mV)
Ambient Temperature 0°C To 55°C: For Full-scale 10 V ±1.0% (±100 mV)
Current InputAmbient Temperature 25°C ±5°C: For Full-scale 16 mA ±0.5% (±80 μA)
Ambient Temperature 0°C To 55°C: For Full-scale 16 mA ±1.0%(±160 μA)
A/D Conversion Time180 μs (Data Is Updated Each Calculation Cycle)
Insulation MethodNo Insulation Between The Analog Input Part And Sequencer Or Between Each Channel
Number Of Occupied Inputs/Outputs0 Points (Maximum Number Of Input/Output Points Is Unrelated)
Applicable SequencersWhen Connecting A FX3S, FX3G (V1.10 or later)
Or FX3S, Expansion Boards Cannot Be Used With The FX3S-CNV-ADP.
Ambient Temperature0 To 55°C - When Operating -20 To 70°C - When Saving
Relative Humidity5% To 95% RH (No Condensation) - When Operating
Vibration-resistantWhen Mounting To DIN RailFrequency: 10 To 57 HzSingle Amplitude: 0.035 mm 10 times In Each Direction X, Y, Z (Total 80 Minutes Each)
Frequency: 57 To 150 HzAcceleration: 4.9 m/s2 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
When Mounting DirectlyFrequency: 10 To 57 HzSingle Amplitude: 0.075 mm 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
Frequency: 57 To 150 HzAcceleration: 9.8 m/s2 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
Shock-resistant147 m/s2, For A Half-sine Pulse Three Times In Directions X, Y, and Z For a Duration of 11 ms
Noise ResistantAchieved Through A Noise Simulator With A Noise Voltage Of 1,000 Vp-p, Noise Width Of 1 μs, Rise Time Of 1 ns, And Frequency Of 30 To 100 Hz
Voltage ResistanceThe Area Between The Analog Input Part And The Sequencer Main Body Is Not Insulated
(Do Not Perform Voltage Resistance Tests)
Insulation ResistanceThe Area Between The Analog Input Part And The Sequencer Main Body Is Not Insulated
(Do Not Perform Insulation Resistance Tests)
Circumstances Of UseWhen There Is Not A Large Amount Of Conductive Dust, And No Corrosion Or Flammable Gas
Frequency Of UseCannot Be Used
In Pressurized Environments Below 2,000 m. Doing So May Cause Failures.

FX3U-4AD

MELSEC-F analog input: related images

Product image

  • 15-bit binary resolution + signed 1-bit (voltage), 14-bit binary + signed 1-bit (voltage) high precision analog input block.
  • A 4-channel voltage input (-10 V to 10 V DC), or a current input (-20 mA to +20 mA, 4 mA DC to 20 mA DC) can be used.
  • Each channel can be designated either voltage or current input.
  • BFM data transfer rate specifications are a maximum of 4 to 5 times faster than standard.
  • 500 μs/ch high speed AD conversion.
  • Equipped with an array of digital filter and peak value hold functions.

Specifications

Analog InputAnalog Input RangeVoltage Input-10 V To +10 V DC (Input Resistance 200 kΩ)
Current Input-20 mA To 20 mA DC, 4 mA To 20 mA DC (Input Resistance 250 Ω)
Number Of Input Channels4 Channels
Absolute Maximum InputVoltage Input±15 V
Current Input±30 mA
Input CharacteristicsInput Mode (Voltage/Current Input) Can Be Set For Each Channel.
Digital OutputVoltage Input15-bit Binary + Signed 1-bit
Current Input14-Bit Binary + Signed 1-bit
ResolutionVoltage Input0.32 mV (20 V × 1/64,000)
2.5 mV (20 V × 1/8,000)
Current Input1.25 μA (40 mA × 1/32,000)
5.00 μA (40 mA × 1/8,000)
Overall PrecisionVoltage InputAmbient Temperature 25°C ±5°C: For Full-scale 20 V ±0.3% (±60 mV)
Ambient Temperature 0°C To 55°C: For Full-scale 20 V ±0.5% (±100 mV)
Current InputAmbient Temperature 25°C ±5°C: For Full-scale 40 mA ±0.5% (±200 μA), 4 mA To 20 mA Input Is The Same (±200 μA)
Ambient Temperature 0°C To 55°C: For Full-scale 40 mA ±1% (±400 μA), 40 mA To 20 mA Is The Same (±400 μA)
A/D Conversion Time500 μs × Number Of Channels Used
(Number Of Channels Used × 5 ms When Using Digital Filters For One Or More Channels)
Insulation Method· The Area Between The Analog Input Part And The Sequencer Is Insulated By A Photocoupler
· The Area Between The Analog Input Part And The Power Supply Is Insulated By A DC/DC Converter
· The Area Between Each Channel Is Uninsulated
Number Of Occupied Inputs/Outputs8 Points (Counted Using Either Input Or Output)
Applicable SequencersFX5U, FX5UC, FX3U (Ver. 2.20 Or Later), FX3UC (Ver 1.30 Or Later For FX3UC-32MT-LT)
<Connecting To A FX5U CPU Unit>
Connecting To A FX5U CPU Unit Requires FX5-CNV-BUS.
<Connecting To A FX5UC CPU Unit>
Connecting To A FX5UC CPU Unit Requires FX5-CNV-BUS Or FX5-CNV-BUSC.
<Connecting To A Connector-type Sequencer>
Connecting To A FX3UC Requires A FX2NC-CNV-IF Or FX3UC-1PS-5V.
Mass0.2 kg
Power Supply5 V DC/110 mA (Internal Power Supply From Sequencer)
24 V DC ±10% 90 mA (External Power Supply)
Ambient Temperature0 To 55°C - When Operating -25 To 75°C - When Saving
Relative Humidity5 To 95% RH (No Condensation) - When Operating
Vibration-resistantWhen Mounting To DIN RailFrequency: 10 To 57 HzSingle Amplitude: 0.035 mm 10 times In Each Direction X, Y, Z (Total 80 Minutes Each)
Frequency: 57 To 150 HzAcceleration: 4.9 m/s2 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
When Mounting DirectlyFrequency: 10 To 57 HzSingle Amplitude: 0.075 mm 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
Frequency: 57 To 150 HzAcceleration: 9.8 m/s2 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
Shock-resistant147 m/s2, For A Half-sine Pulse Three Times In Directions X, Y, and Z For a Duration of 11 ms
Noise ResistantAchieved Through A Noise Simulator With A Noise Voltage Of 1,000 Vp-p, Noise Width Of 1 μs, Rise Time Of 1 ns, And Frequency Of 30 To 100 Hz
Voltage ResistanceBetween All Terminals At Once And Earth Terminal: 500 V AC For One Minute
Insulation ResistanceBetween All Terminals At Once And Earth Terminal: 5 MΩ Or More At 500 V DC On An Insulation Resistance Meter
GroundingD-type Grounding (Grounding Resistance: 100 Ω Or Less) <No Common Grounding With Power Systems Required>
Use Dedicated Or Shared Grounding.
Circumstances Of UseWhen There Is Not A Large Amount Of Conductive Dust, And No Corrosion Or Flammable Gas
Frequency Of UseCannot Be Used
In Pressurized Environments Below 2,000 m. Doing So May Cause Failures.

FX3U-4AD-ADP

MELSEC-F analog input: related images

Product image

  • 12-bit binary resolution (voltage), 11-bit binary (current) high precision analog input adapter.
  • A 4-channel voltage input (0 V to 10 V DC), or a current input (4 to 20 mA DC) can be used.
  • Each channel can be designated either voltage or current input.
  • Programless (no dedicated commands), so forwarding of data is possible.

Specifications

Analog InputAnalog Input RangeVoltage Input0 V To 10 V DC (Input Resistance 194 kΩ)
Current Input4 mA To 20 mA DC (Input Resistance 250 Ω)
Number Of Input Channels4 Channels
Absolute Maximum InputVoltage Input-0.5 V, +15 V
Current Input-2 mA, +30 mA
Input CharacteristicsInput Mode (Voltage/Current Input) Can Be Set For Each Channel.
Digital OutputVoltage Input12-bit Binary
Current Input11-bit Binary
ResolutionVoltage Input2.5 mV (10 V × 1/4,000)
Current Input10 μA (16 mA × 1/1,600)
Overall PrecisionVoltage InputAmbient Temperature 25°C ±5°C: For Full-scale 10 V ±0.5% (±50 mV)
Ambient Temperature 0°C To 55°C: For Full-scale 10 V ±1.0% (±100 mV)
Current InputAmbient Temperature 25°C ±5°C: For Full-scale 16 mA ±0.5% (±80 μA)
Ambient Temperature 0°C To 55°C: For Full-scale 16 mA ±1.0%(±160 μA)
A/D Conversion TimeFX3U/FX3UC Sequencer200 μs (Data Is Updated Each Calculation Cycle)
FX3S/FX3G/FX3GC Sequencer250 μs (Data Is Updated Each Calculation Cycle)
Insulation Method· The Area Between The Analog Input Part And The Sequencer Is Insulated By A Photocoupler
· The Area Between The Analog Input Part And The Power Supply Is Insulated By A DC/DC Converter
· The Area Between Each Channel Is Uninsulated
Number Of Occupied Inputs/Outputs0 Points (Maximum Number Of Input/Output Points Is Unrelated)
Applicable SequencersFX3S, FX3G, FX3U, FX3GC, FX3UC(Ver 1.20 Or Later For FX3UC-32MT-LT)
Connection To FX3S Requires FX3S-CNV-ADP.
Connection To FX3G Requires FX3G-CNV-ADP.
Connection To FX3U Or FX3UC-32MT-LT (-2) Requires A Function Expansion Board.
Mass0.1 kg
Power Supply5 V DC 15 mA (Internal Power Supply From Sequencer)
24 V DC +20% -15% 40 mA (External Power Supply)
Ambient Temperature0 To 55°C - When Operating -25 To 75°C - When Saving
Relative Humidity5 To 95% RH (No Condensation) - When Operating
Vibration-resistantWhen Mounting To DIN RailFrequency: 10 To 57 HzSingle Amplitude: 0.035 mm 10 times In Each Direction X, Y, Z (Total 80 Minutes Each)
Frequency: 57 To 150 HzAcceleration: 4.9 m/s2 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
When Mounting DirectlyFrequency: 10 To 57 HzSingle Amplitude: 0.075 mm 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
Frequency: 57 To 150 HzAcceleration: 9.8 m/s2 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
Shock-resistant147 m/s2, For A Half-sine Pulse Three Times In Directions X, Y, and Z For a Duration of 11 ms
Noise ResistantAchieved Through A Noise Simulator With A Noise Voltage Of 1,000 Vp-p, Noise Width Of 1 μs, Rise Time Of 1 ns, And Frequency Of 30 To 100 Hz
Voltage ResistanceBetween All Terminals At Once And Earth Terminal: 500 V AC For One Minute
Insulation ResistanceBetween All Terminals At Once And Earth Terminal: 5 MΩ Or More At 500 V DC On An Insulation Resistance Meter
GroundingD-type Grounding (Grounding Resistance: 100 Ω Or Less) <No Common Grounding With Power Systems Required>
Use Dedicated Or Shared Grounding.
Circumstances Of UseWhen There Is Not A Large Amount Of Conductive Dust, And No Corrosion Or Flammable Gas
Frequency Of UseCannot Be Used
In Pressurized Environments Below 2,000 m. Doing So May Cause Failures.

FX3UC-4AD

MELSEC-F analog input: related images

Product image

  • 15-bit binary resolution + signed 1-bit (voltage), 14-bit binary + signed 1-bit (voltage) high precision analog input block.
  • A 4-channel voltage input (-10 V to 10 V DC), or a current input (-20 to 20 mA DC, 4 to 20 mA DC) can be used.
  • Each channel can be designated either voltage or current input.
  • BFM data transfer rate specifications are a maximum of 9 times faster than standard.
  • 500 μs/ch high speed AD conversion.
  • Equipped with an array of digital filter and peak value hold functions.

Specifications

Analog InputAnalog Input RangeVoltage Input-10 V To +10 V DC (Input Resistance 200 kΩ)
Current Input-20 mA To +20 mA, 4 mA To 20 mA DC (Input Resistance 250 Ω)
Number Of Input Channels4 Channels
Absolute Maximum InputVoltage Input±15 V
Current Input±30 mA
Input CharacteristicsInput Mode (Voltage/Current Input) Can Be Set For Each Channel.
Digital OutputVoltage Input15-bit Binary + Signed 1-bit
Current Input14-Bit Binary + Signed 1-bit
ResolutionVoltage Input0.32 mV (20 V × 1/64,000)
2.5 mV (20 V × 1/8,000)
Current Input1.25 μA (40 mA × 1/32,000)
5.00 μA (40 mA × 1/8,000)
Overall PrecisionVoltage InputAmbient Temperature 25°C ±5°C: For Full-scale 20 V ±0.3% (±60 mV)
Ambient Temperature 0°C To 55°C: For Full-scale 20 V ±0.5% (±100 mV)
Current InputAmbient Temperature 25°C ±5°C: For Full-scale 40 mA ±0.5% (±200 μA), 4 mA To 20 mA Input Is The Same (±200 μA)
Ambient Temperature 0°C To 55°C: For Full-scale 40 mA ±1% (±400 μA), 40 mA To 20 mA Is The Same (±400 μA)
A/D Conversion Time500 μs × Number Of Channels Used
(Number Of Channels Used × 5 ms When Using Digital Filters For One Or More Channels)
Insulation Method· The Area Between The Analog Input Part And The Sequencer Is Insulated By A Photocoupler
· The Area Between The Analog Input Part And The Power Supply Is Insulated By A Transformer
· The Area Between Each Channel Is Uninsulated
Number Of Occupied Inputs/Outputs8 Points (Counted Using Either Input Or Output)
Applicable SequencersFX3UC (Ver.1.30 Or Later For FX3UC-32MT-LT)
Mass0.13 kg
Power Supply5 V DC 100 mA (Internal Power Supply From Sequencer)
24 V DC ±10% 80 mA (External Power Supply)
Ambient Temperature0 To 55°C - When Operating -25 To 75°C - When Saving
Relative Humidity5 To 95% RH (No Condensation) - When Operating
Vibration-resistantWhen Mounting To DIN RailFrequency: 10 To 57 HzSingle Amplitude: 0.035 mm 10 times In Each Direction X, Y, Z (Total 80 Minutes Each)
Frequency: 57 To 150 HzAcceleration: 4.9 m/s2 10 Times In Each Direction X, Y, Z (Total 80 Minutes Each)
Shock-resistant147 m/s2, For A Half-sine Pulse Three Times In Directions X, Y, and Z For a Duration of 11 ms
Noise ResistantAchieved Through A Noise Simulator With A Noise Voltage Of 1,000 Vp-p, Noise Width Of 1 μs, Rise Time Of 1 ns, And Frequency Of 30 To 100 Hz
Voltage ResistanceBetween All Terminals At Once And Earth Terminal: 500 V AC For One Minute
Insulation ResistanceBetween All Terminals At Once And Earth Terminal: 5 MΩ Or More At 500 V DC On An Insulation Resistance Meter
GroundingD-type Grounding (Grounding Resistance: 100 Ω Or Less) <No Common Grounding With Power Systems Required>
Use Dedicated Or Shared Grounding.
Circumstances Of UseWhen There Is Not A Large Amount Of Conductive Dust, And No Corrosion Or Flammable Gas
Frequency Of UseCannot Be Used
In Pressurized Environments Below 2,000 m. Doing So May Cause Failures.
Part Number
FX3G-2AD-BD
FX3U-4AD
FX3U-4AD-ADP
FX3UC-4AD
FX5-4AD-ADP
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipInput Type Number of Input Channels A/D Conversion Speed (Conversion Time) Representative Standard Type of unit Applicable sequencer Number of input channels
(ch)
Voltage input range Current input range

SGD 91.10

1 Piece(s) 91 Day(s) Voltage / Current2100 to Less Than 500 μSCEAnalog Input BoardFX3S/FX3G2DC0 to 10VDC 4–20 mA

-

1 Piece(s) Quote Voltage / Current4100 to Less Than 500 μSCEAnalog Input BlockFX5U/FX5UC/FX3U/FX3UC4DC-10 to 10VDC-20 to 20 mA / DC4 to 20 mA

SGD 402.20

1 Piece(s) 91 Day(s) Voltage / Current4100 to Less Than 500 μSCEAnalog Input AdapterFX3S/FX3G/FX3U/FX3GC/FX3UC4DC0 to 10VDC 4–20 mA

SGD 557.80

1 Piece(s) 91 Day(s) Voltage / Current4Less than 0.5 to 1 msCEAnalog Input BlockFX3UC4DC-10V to 10VDC-20 to 20 mA / DC4 to 20 mA

SGD 456.40

1 Piece(s) 91 Day(s) Voltage / Current4100 to Less Than 500 μSCE / UL / CULAnalog input--DC -10V to 10VDC -20 to 20 mA

Loading...

  1. 1
 

Basic Information

Type Input Input Range Other Terminal shape Terminal Block

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)