(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Instead, please kindly use other browsers like Google Chrome, Microsoft Edge or Mozilla Firefox.
A wide variety of standard and configurable components for factory automation engineers in industries such as automotive, semiconductor, packaging, medical and many more.
A good selection of accessories such as screws, bolts, washers and nuts that you may need for your daily engineering usage.
Browse industrial materials ranging from heat insulating plates, sponges, to metal and plastic materials in different sizes to meet your various applications.
A wide variety of wiring parts for connecting and protecting control and PC parts including Connectors, Cables, Electric Wires, Crimping Terminals and more.
A wide variety of controls and PC parts for electrical engineers including Controls, Powers, PC parts and more.
A wide variety of cutting tools for many uses and work materials including End Mills, Drills, Cutters, Reamers, Turning Tools and more.
A wide variety of tools and supplies used in processing including Machine Tools, Measurement Tools, Grinding and Polishing Supplies and more.
A wide variety of goods used in shipment, material handling and warehouse including Tape supplies, Stretch film, Truck, Shelf, Crane and more.
A large variety of goods for every kind of factories and offices including Protection items, Cleaning supplies, sanitations, office supplies and more.
A large variety of items used in R&D and Clean Room including research Equipment, Laboratory Essentials, Analysis Supplies, Clean Environment-Related Equipment and more.
Choose from thousands of standard stamping die components including Punch & Die, Gas Springs, Guide Components, Coil Springs and many more.
Browse our wide variety of mold components including Ejector Pins, Sleeves, Leader Components, Sprue Bushings and many more.
Browse our injection molding components including Heating Items, Couplers, Hoses and more.
Micro sequencer MELSEC-F series CC-Link
Part Number
Configured Part Number is shown.
FX2N-32CCL
FX sequencers can be connected as a CC-Link remote device station.
This permits distributed control and centralized management of lines.
CC-Link Version | Ver. 1.00 |
---|---|
Station Type | Remote device station |
Insulation Method | The network bus and the internal power supply are insulated by a opto-isolator |
Transmission Speed | Selectable from 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps (set with a rotary switch) |
Station Number | 1 to 64 stations (set with a rotary switch) |
Number of Occupied Stations | 1 to 4 stations (set with a rotary switch) |
Maximum Total Cable Extension (Maximum Transmission Distance) | Maximum 1,200 m; varies depending on the transmission speed |
Number of Remote Inputs/Outputs | There are 32 remote input points and 32 remote output points per station. Note that the upper 16 points of the last station are occupied by the CC-Link system as the system area. |
Number of Remote Register Points | There are 4 remote register points in the RW write area, and 4 remote register points in the RW read area, per station. |
Link Points Per Station | 32 remote input points / 32 remote output points (RX/RY) Note that the upper 16 points of the last station are occupied by the CC-Link system as the system area. 4 remote register (RWw) points (Master station > Remote device station) 4 remote register (RWr) points (Remote device station > Master station) |
Communication Method | Polling method |
Synchronization Method | Frame synchronization method |
Encryption Method | NRZI method |
Transmission Path Type | Bus (RS-485) |
Transmission Format | HDLC-compliant |
Error Control Method | CRC(X16 + X12 + X5 + 1) |
Connection Cable | Dedicated CC-Link cable, dedicated CC-Link high-performance cable The dedicated CC-Link cable and dedicated CC-Link high-performance cable cannot be used at the same time. |
Communication With Sequencers | Communication is performed using FROM/TO commands via buffer memory |
Display (LED) | RD, SD, L RUN, L ERR, POWER |
Number of Occupied Inputs/Outputs | 8 points (may be counted using either input or output) |
Applicable Sequencers | FX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UC "Connection to connector type sequencer" FX2NC-CNV-IF is required to connect to the FX1NC or FX2NC. Either FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect to the FX3GC or FX3UC. |
Weight | 0.2 kg |
Power Supply | 5 V DC internal power supply: Energized from the sequencer via an extension cable. 24 V DC external power supply (24 V DC ± 10%): Energized from the external terminal block. |
---|---|
Current Consumption | 5 V DC internal power supply: 130 mA 24 V DC external power supply: 50 mA |
The FX3U-64CCL type CC-Link interface block is a special expansion block for connecting an FX5U/FX5UC CPU unit or FX3G/FX3U/FX3GC/FX3UC sequencer to CC-Link. (Compatible with CC-Link V2)
The FX3U-64CCL operates as an intelligent device station over CC-Link.
Only one FX3U-64CCL unit can be connected to one sequencer base unit.
The GX Developer can be used to access an FX5U/FX5UC CPU unit or FX3G/FX3U/FX3GC/FX3UC sequencer base unit to which the FX3U-64CCL is connected, from the Q master station / local station via CC-Link. (GX Developer of Ver. 8.76E or later is supported)
CC-Link Version | Ver. 2.00 (Ver. 1.10 is also supported) |
---|---|
Station Type | Intelligent device station |
Insulation Method | The network bus and the internal power supply are insulated by a opto-isolator |
Transmission Speed | Selectable from 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps Selectable (Set with a rotary switch.) |
Station Number | 1 to 64 stations (set with a rotary switch) |
Number of Occupied Stations | 1 to 4 stations (set with a rotary switch) |
Maximum Total Cable Extension (Maximum Transmission Distance) | According to the CC-Link specification. |
Number of Remote Inputs/Outputs | There are 32 remote input points and 32 remote output points per station. (Expanded cyclic settings of × 1 to × 8 are available) Note that the upper 16 points of the last station are occupied by the CC-Link system as the system area. |
Number of Remote Register Points | There are 4 remote register points in the RW write area, and 4 remote register points in the RW read area, per station. (Expanded cyclic settings of × 1 to × 8 are available) |
Communication Method | Broadcast polling method |
Synchronization Method | Flag synchronization method |
Encryption Method | NRZI method |
Transmission Path Type | Bus (RS-485) |
Transmission Format | HDLC-compliant |
Error Control Method | CRC(X16 + X12 + X5 + 1) |
Connection Cable | Dedicated CC-Link cable, dedicated CC-Link high-performance cable and dedicated CC-Link cable compatible with Ver. 1.10 Different cables cannot be used at the same time. |
Communication With Sequencers | Communication is performed using FROM/TO commands via buffer memory (or based on direct specification of buffer memory) |
Display (LED) | RD, SD, RUN, ERR., L RUN, L ERR., POWER |
Number of Occupied Inputs/Outputs | 8 points (may be counted using either input or output) |
Applicable Sequencers | FX5U, FX5UC, FX3G, FX3U, FX3GC, FX3UC (Ver. 2.20 SER No.55**** Units produced in or after May 2005) * Only one 64CCL unit can be connected to one sequencer base unit. "Connection to FX5U and FX5UC CPU units" Either FX5-CNV-BUS or FX5-CNV-BUSC is required to connect to the FX5U or FX5UC. Select either one according to the system configuration. "Connection to connector type sequencer" Either FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect to the FX3GC and FX3UC. |
Weight | 0.3 kg |
Power Supply | 5 V DC internal power supply: 5 V DC from the sequencer is not used. (5 V DC is converted from a 24 V DC external power supply) 24 V DC external power supply: Energized from the external terminal block. (+20%, -15%; ripple ratio (p-p): within 5%) |
---|---|
Allowable Momentary Power Outage Duration | PS1: Operation continues after a momentary power outage of 1 ms or less |
Current Consumption | 220 mA |
Special expansion block to use FX5U/FX5UC CPU unit or FX3G/FX3U/FX3GC/FX3UC sequencer as the CC-Link master station.
Up to 8 remote I/O stations and up to 8 remote device stations or intelligent device stations can be connected to the master station. (Up to 4 stations available for FX3G/FX3GC sequencer)
By using the FX3U-16CCL-M type CC-Link master block and the FX3U-64CCL type CC-Link interface block, a CC-Link V2 system can be configured using only FX sequencers.
CC-Link Version | Ver. 2.00 (Ver. 1.10 is also supported) | |
---|---|---|
Station Type | Master station (no local station or standby master station function) | |
Transmission Speed | Selectable from 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps (set with a rotary switch) | |
Station Number | No. 0 (set with a rotary switch) | |
Maximum Total Cable Extension (Maximum Transmission Distance) | Maximum 1,200 m; varies depending on the transmission speed | |
Maximum Number of Connected Stations | Remote I/O Stations | Up to 8 stations (actual 32 input/output points of sequencer are occupied per station) |
Total of Remote Device Stations + Intelligent Device Stations | Up to 8 stations (total points for each of RX or RY shall be 256 or less) | |
Maximum Input/Output Points Per System | FX3U/FX3UC Sequencer | Total of 1) + 2) below ≤ 384 points 1) (Actual number of sequencer input/output points) + (Number of occupied special expansion block input/output points) + (Number of occupied 16CCL-M input/output points: 8 points) ≤ 256 points 2) 32 × Number of remote I/O stations ≤ 256 points |
FX3G/FX3GC Sequencer | 32 × Number of remote I/O stations ≤ 128 points | |
Link Points Per Station | Remote inputs/outputs (RX, RY): 32 points Remote registers (RWw): 4 points (Master station > Remote device station / intelligent device station) Remote registers (RWr): 4 points (Remote device station / intelligent device station > Master station) *The above are the number of link points in the Remote Net Ver. 1 mode. | |
Communication Method | Broadcast polling method | |
Synchronization Method | Frame synchronization method | |
Encryption Method | NRZI method | |
Transmission Path Type | Bus (RS-485) | |
Transmission Format | HDLC-compliant | |
Error Control Method | CRC(X16 + X12 + X5 + 1) | |
Connection Cable | Dedicated CC-Link cable / Dedicated CC-Link high-performance cable / Dedicated CC-Link cable compatible with Ver. 1.10 Using the dedicated CC-Link cable, dedicated CC-Link high-performance cable and dedicated CC-Link cable compatible with Ver. 1.10 cannot be done at the same time. Also, install a terminating resistor corresponding to the type of cable. | |
RAS Function | · Auto-reset function · Slave-station isolation function · Error detection by special link relay / register | |
Communication With Sequencers | Communication is performed via buffer memory using FROM/TO commands or direct specification of buffer memory (FX3U/FX3UC), etc. | |
Display (LED) | RUN, ERR., L RUN, L ERR. , SD, RD, POWER | |
Number of Occupied Inputs/Outputs | 8 points (may be counted using either input or output) | |
Applicable Sequencers | FX5U, FX5UC, FX3G, FX3U (Ver. 2.20 or later), FX3GC, FX3UC (Ver. 2.20 or later) Using the FX3U-16CCL-M and FX2N-16CCL-M at the same time cannot be done with the FX2N-32ASI-M. The FX3U-16CCL-M and FX2N-16CCL-M cannot be used together. "Connection to FX5U and FX5UC CPU units" Either FX5-CNV-BUS or FX5-CNV-BUSC is required to connect to the FX5U or FX5UC. Select either one according to the system configuration. "Connection to connector type sequencer" Either FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect to the FX3GC and FX3UC. | |
Weight | 0.3 kg |
Power Supply | External Power Supply | 24 V DC +20%, -15%; ripple (p-p): within 5% |
---|---|---|
Internal Power Supply | 5 V 5 V DC from the sequencer is not used. (5 V DC is converted from the 24 V DC external power supply for energization) Follow the power input timing and procedure. | |
Current Consumption | 24 V DC external power supply: 240 mA |
Part Number |
---|
FX2N-32CCL |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Representative Standard | Applicable sequencer | Type of unit | CC-Link version |
---|---|---|---|---|---|---|---|---|
SGD 495.50 | 1 Piece(s) | 91 Day(s) | CE | FX1N / FX1NC / FX2N / FX2NC / FX3G / FX3GC / FX3U / FX3UC | CC-Link Remote Device Station | Ver.1.00 |
Loading...
Communication Interface (Transmission Standard) | Other | Transmission Speed | 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps Available (Set with Rotary Switch) |
---|
Please check the type/dimensions/specifications of the part FX2N-32CCL in the MELSEC-F Series Data Link / Communication Unit series.
Part Number |
---|
FX3U-16CCL-M |
FX3U-64CCL |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Representative Standard | Applicable sequencer | Type of unit | CC-Link version |
---|---|---|---|---|---|---|---|---|
SGD 300.80 | 1 Piece(s) | 20 Day(s) | CE / UL | FX5U, FX5UC, FX3G, FX3U (Ver. 2.20 or Later), FX3GC, FX3UC (Ver. 2.20 or Later) | CC-Link Master Station | Ver.2.00 | ||
SGD 294.10 | 1 Piece(s) | 91 Day(s) | CE / UL | FX5U, FX5UC, FX3G, FX3U, FX3GC, FX3UC (Ver. 2.20 SER No. 55**** - Products Produced After May 2005) | CC-Link Intelligent Device Station | Ver.2.00 |
How can we improve?
How can we improve?