CC-Link Analog Input/Output (Input) Unit (AJ65SBT-64AD)

CC-Link Analog Input/Output (Input) Unit AJ65SBT-64AD

An analog input unit for the in-line field network CC-Link.

PDF

Part Number

Configured Part Number is shown.

AJ65SBT-64AD

AJ65BT-64AD Specifications

Number of Analog Input Points4 points (4 channels)
Analog InputVoltage-10 to +10 V DC (input resistance: 1 MΩ)
Current-20 to +20 mA DC (input resistance: 250 Ω)
Digital Output0 to 4,000, -2,000 to +2,000
Input/Output Characteristics, ResolutionInput RangeDigital Output Value (Maximum Resolution)
Voltage Input-10 to 10 V0 to 4,000 or -2,000 to 2,000 (5 mV)
0 to 10 V0 to 4,000 or -2,000 to 2,000 (2.5 mV)
0 to 5 V0 to 4,000 or -2,000 to 2,000 (1.25 mV)
1 to 5 V0 to 4,000 or -2,000 to 2,000 (1.0 mV)
Current Input-20 to 20 mA0 to 4,000 or -2,000 to 2,000 (20 μA)
0 to 20 mA0 to 4,000 or -2,000 to 2,000 (10 μA / 5 μA)
4 to 20 mA0 to 4,000 or -2,000 to 2,000 (4 μA)
Accuracy (Accuracy With Respect to Maximum Digital Output Value)Ambient Temperature: 0 to 55°C±1%
A/D Conversion Speed1 ms / channel
Absolute Maximum InputVoltage±15 V
Current±30 mA
Insulation MethodBetween power supply / communication system and analog input: opto-isolator insulation
Between channels: non-insulated
Dielectric StrengthBetween power supply / communication system at once and all analog inputs at once: 500 V AC for 1 minute
Insulation ResistanceBetween all power supply / communication systems at once and all analog inputs at once: 10 MΩ or more at 500 V DC on an insulation resistance tester
Station TypeRemote device station (Ver. 1 remote device station)
Number of Occupied Stations2 stations
Unit Power SupplyVoltage24 V DC (18 to 30 V DC)
Current0.12 A (when 24 V DC)
External Wiring Connection MethodCommunication part, unit power supply part: 7-point 2-piece terminal block (M3.5 screw)
Input/output part: 27-point 2-piece terminal block (M3.5 screw)
External DimensionsHeight (H)65 mm
Width (W)151.9 mm
Depth (D)63 mm
Weight0.35 kg

AJ65SBT-64AD Specifications

Number of Analog Input Points4 points (4 channels)
Analog InputVoltage-10 to +10 V DC (input resistance: 1 MΩ)
Current0to 20 mA DC (input resistance: 250 Ω)
Digital Output-4,096 to +4,095
Input/Output Characteristics, ResolutionInput RangeDigital Output Value (Maximum Resolution)
Voltage Input-10 to 10 V-4,000 to 4,000 (2.5 mV)
User Range Setting 1
(-10 to 10 V)
-4,000 to 4,000 (2.5 mV)
0 to 5 V0 to 4,000 (1.25 mV)
1 to 5 V0 to 4,000 (1.0 mV)
User Range Setting 2
(0 to 5 V)
0 to 4,000 (1.0 mV)
Current Input0 to 20 mA0 to 4,000 (5 μA)
4 to 20 mA0 to 4,000 (4 μA)
User Range Setting
(0 to 20 mA)
0 to 4,000 (4 μA)
Accuracy (Accuracy With Respect to Maximum Digital Output Value)Ambient Temperature: 25±5°C±0.2%
Ambient Temperature: 0 to 55°C±0.4%
A/D Conversion Speed1 ms / channel
Absolute Maximum InputVoltage±15 V
Current±30 mA
Insulation MethodBetween communication system and all analog inputs at once: opto-isolator insulation
Between power supply system and all analog inputs at once: opto-isolator insulation
Between channels: non-insulated
Dielectric StrengthBetween power supply / communication system at once and all analog inputs at once: 500 V AC for 1 minute
Station TypeRemote device station (Ver. 1 remote device station)
Number of Occupied Stations1 station
Unit Power SupplyVoltage24 V DC (20.4 to 26.4 V DC)
Current0.090 A (at 24 V DC)
Inrush Current8.5 A, 2.3 ms or less
External Wiring Connection MethodCommunication part, unit power supply part: 7-point 2-piece terminal block (M3 screw)
Input/output part: 18-point direct attachment terminal block (M3 screw)
External DimensionsHeight (H)50 mm
Width (W)118 mm
Depth (D)40 mm
Weight0.20 kg

AJ65VBTCU-68ADIN Specifications

Number of Analog Input Points8 points (8 channels)
Analog InputVoltage0to 20 mA DC (input resistance: 250 Ω)
Digital Output-96 to +4,095
Input/Output Characteristics, ResolutionInput RangeDigital Output Value (Maximum Resolution)
Current Input0 to 20 mA0 to 4,000 (5 μA)
4 to 20 mA0 to 4,000 (4 μA)
User Range Setting
(0 to 20 mA)
0 to 4,000 (4 μA)
Accuracy (Accuracy With Respect to Maximum Digital Output Value)Ambient Temperature: 25±5°C±0.3%
Ambient Temperature: 0 to 55°C±0.2%
A/D Conversion Speed1 ms / channel
Absolute Maximum InputCurrent±30 mA
Insulation MethodBetween communication system and all analog inputs at once: opto-isolator insulation
Between power supply system and all analog inputs at once: transformer insulation
Between channels: non-insulated
Dielectric StrengthBetween power supply / communication system at once and all analog inputs at once: 500 V AC for 1 minute
Protection GradeIP1XB
Station TypeRemote device station (Ver. 1 remote device station or Ver. 2 remote device station)
Number of Occupied StationsFor Ver. 1 remote device station: 3 stations
For Ver. 2 remote device station: 1 station (expansion cyclic setting: multiplied by 4)
Communication CableVer. 1.10 supported CC-Link dedicated cable: FANC-110SBH, FA-CBL200PSBH, CS-110
Unit Power SupplyVoltage24 V DC (20.4 to 26.4 V DC; ripple ratio: within 5%)
Current0.10 A (when 24 V DC)
Inrush Current4.2 A, 1.2 ms or less
External Wiring Connection MethodCommunication part: single-action connector for communication (sold separately)
Unit power supply part: single-action connector for FG / power supply (sold separately)
Input/output part: single-action connector for I/O (sold separately)
External DimensionsHeight (H)115 mm
Width (W)41 mm
Depth (D)67 mm
Weight0.17 kg

AJ65VBTCU-68ADVN Specifications

Number of Analog Input Points8 points (8 channels)
Analog InputVoltage-10 to +10 V DC (input resistance: 1 MΩ)
Digital Output-4,096 to +4,095
Input/Output Characteristics, ResolutionInput RangeDigital Output Value (Maximum Resolution)
Voltage Input-10 to 10 V-4,000 to 4,000 (2.5 mV)
User Range Setting 1
(-10 to 10 V)
-4,000 to 4,000 (2.5 mV)
0 to 5 V0 to 4,000 (1.25 mV)
1 to 5 V0 to 4,000 (1.0 mV)
User Range Setting 2
(0 to 5 V)
0 to 4,000 (1.0 mV)
Accuracy (Accuracy With Respect to Maximum Digital Output Value)Ambient Temperature: 25±5°C±0.3%
Ambient Temperature: 0 to 55°C±0.2%
A/D Conversion Speed1 ms / channel
Absolute Maximum InputVoltage±15 V
Insulation MethodBetween communication system and all analog inputs at once: opto-isolator insulation
Between power supply system and all analog inputs at once: transformer insulation
Between channels: non-insulated
Dielectric StrengthBetween power supply / communication system at once and all analog inputs at once: 500 V AC for 1 minute
Protection GradeIP1XB
Station TypeRemote device station (Ver. 1 remote device station or Ver. 2 remote device station)
Number of Occupied StationsFor Ver. 1 remote device station: 3 stations
For Ver. 2 remote device station: 1 station (expansion cyclic setting: multiplied by 4)
Communication CableVer. 1.10 supported CC-Link dedicated cable: FANC-110SBH, FA-CBL200PSBH, CS-110
Unit Power SupplyVoltage24 V DC (20.4 to 26.4 V DC; ripple ratio: within 5%)
Current0.10 A (when 24 V DC)
Inrush Current4.2 A, 1.2 ms or less
External Wiring Connection MethodCommunication part: single-action connector for communication (sold separately)
Unit power supply part: single-action connector for FG / power supply (sold separately)
Input/output part: single-action connector for I/O (sold separately)
External DimensionsHeight (H)115 mm
Width (W)41 mm
Depth (D)67 mm
Weight0.17 kg
Part Number
AJ65SBT-64AD
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipInput Type Number of Input Channels Terminal shape Voltage input range Current input range

SGD 389.80

1 Piece(s) 20 Day(s) Voltage / Current4Terminal BlockDC-10V to 10VDC 0–20 mA

Loading...

  1. 1
 

Basic Information

Type Input A/D Conversion Speed (Conversion Time) Less than 1 to 10 mS Representative Standard UL

Please check the type/dimensions/specifications of the part AJ65SBT-64AD in the CC-Link Analog Input/Output (Input) Unit series.

Similar Part Numbers

Part Number
AJ65BT-64AD
AJ65VBTCU-68ADIN
AJ65VBTCU-68ADVN
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipInput Type Number of Input Channels Terminal shape Voltage input range Current input range

SGD 569.50

1 Piece(s) 90 Day(s) Voltage / Current4Terminal BlockDC-10V to 10V-20 DC to 20 mA

SGD 626.20

1 Piece(s) Quote Current8Connector-DC 0–20 mA

SGD 626.20

1 Piece(s) Quote Voltage8ConnectorDC-10V to 10V-

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)