CC-Link Analog Input Unit Terminal Block Type

CC-Link Analog Input Unit Terminal Block Type

CC-Link/LT analog input unit.
[Features]
・ Since the number of input/output points (number of occupied stations) changes depending on the last channel for which conversion is enabled, the number of input/output points (number of occupied stations) can be saved
・ Dedicated flat cable is directly mounted to the unit (50 cm)
・ 4 channels
・ Input: -10 to 10 V DC, 0 to 20 mA DC
・ output (Resolution): 0 to 4,000, -4,000 to 4,000
・ Conversion Speed: 200 μs / 4 channels
・ Number Of Occupied Stations: 16-point mode 4 stations
[Applications]
・ Network communication

PDF

Part Number

Configured Part Number is shown.

CL2AD4-B

CC-Link Analog Input Unit Terminal Block Type Specifications

CL2AD4-B external appearance

CL2AD4-B external appearance

CL2AD4-B dimensional outline drawing (unit: mm)

CL2AD4-B dimensional outline drawing (unit: mm)

Performance Specifications

Analog Input Points4 points (4 channels)
Analog InputVoltage-10 to +10 V DC (input resistance: 11 MΩ)
Current0 to 20 mA DC (input resistance: 250 Ω)
Digital Output-4,096 to +4,095
Input/Output Characteristics, ResolutionInput RangeDigital Output Value (Maximum Resolution)
Voltage Input0 To 10 V0 to 4,000 (2.5 mV)
0 To 5 V0 to 4,000 (1.25 mV)
1 To 5 V0 to 4,000 (1.0 mV)
-10 To 10 V-4,000 to 4,000 (2.5 mV)
Current Input0 To 20 mA0 to 4,000 (5 μA)
4 To 20 mA0 to 4,000 (4 μA)
Precision (Precision With Respect To Maximum Digital Output Value)Ambient Temperature: 25±5°C±0.2%
Ambient Temperature: 0 To 55°C±0.4%
Temperature Coefficient±80 ppm/°C (0.0080%/°C)
A/D Conversion Speed200 µs / 4 channels
Absolute Maximum InputVoltage±15 V
Current±30 mA
Isolation MethodBetween communication system and all analog inputs at once: photocoupler insulation, transformer insulation
Between power supply system and all analog inputs at once: photocoupler insulation, transformer insulation
Between communication system and power supply system: photocoupler insulation, transformer insulation
Between channels: non-insulation
Dielectric StrengthBetween communication system and all analog inputs at once, between power supply system and all analog inputs at once, between communication system and power supply system: 500 V AC for 1 minute
Insulation ResistanceBetween communication system and all analog inputs at once, between power supply system and all analog inputs at once, between communication system and power supply system: 10 MΩ or more at 500 V DC
Protection GradeIP2X
Number Of Occupied Stations4 stations in 16-point mode
Unit Power SupplyVoltage24 V DC (20.4 to 28.8 V DC, Ripple Ratio within 5%)
Current70 mA
Current At Startup570 mA
External Wiring Connection Method14-point Direct Attachment Terminal Block (M3 Screw)
Mass0.15 kg

General Specifications

Ambient Operating Temperature0 to 55℃
Ambient Storage Temperature-25 to 75℃
Ambient Operating Humidity5 to 95% RH, assuming no condensation
Ambient Storage Humidity5 to 95% RH, assuming no condensation
Vibration ResistanceJIS B 3502, IEC 61131-2 compliantUnder Intermittent VibrationFrequency: 5 to 8.4 Hz, Amplitude: 3.5 mm
Frequency: 8.4 to 150 Hz, Acceleration: 9.8 m/s2
Sweeps: 10 sweeps in each direction of X, Y and Z
Under Continuous VibrationFrequency: 5 to 8.4 Hz, Amplitude: 1.75 mm
Frequency: 8.4 to 150 Hz, Acceleration: 4.9 m/s2
Impact ResistanceConforms to JIS B 3502, IEC 61131-2 (147 m/s2, 3 sweeps in 3 directions of X, Y and Z)
Operating AtmosphereNo corrosive gas
Operating Altitude0 to 2,000 m
Installation LocationInside the control panel
Overvoltage CategoryII or lower
Pollution Degree2 or less
Part Number
CL2AD4-B
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to Ship

-

1 Piece(s) Quote

Loading...

  1. 1
 

Basic Information

Type Input Input Type Voltage / Current Number of Input Channels 4
A/D Conversion Speed (Conversion Time) 100 to Less Than 500 μS Terminal shape Terminal Block Representative Standard CE / UL
Voltage input range DC-10V to 10V Current input range DC 0–20 mA

Please check the type/dimensions/specifications of the part CL2AD4-B in the CC-Link Analog Input Unit Terminal Block Type series.

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)