Dedicated CC-Link/LT Power Supply

Dedicated CC-Link/LT Power Supply

A dedicated power supply for supplying stable power from an external power supply to the CC-Link/LT system (DC24V).

PDF

Part Number

Configured Part Number is shown.

CL1PSU-2A

Dedicated CC-Link/LT Power Supply Specifications

Dedicated CC-Link/LT Power Supply: related image

CL1PSU-2A external appearance

Dedicated CC-Link/LT Power Supply: related image

CL1PSU-2A dimensional drawing, unit: mm

InputRated Voltage100/120/200/230/240 V AC
Allowable Voltage Range85 to 264 V AC
Rated Current1.2 A / 100 V AC, 0.7 A / 200 V AC
Rated Frequency50/60 Hz
Power Supply Fuse3.15 A
Inrush CurrentMax. 50 A / 100 V AC, Max. 60 A / 200 V AC
OutputOutput Voltage24 V DC +10%/-5%
Output Current0.01 to 2 A, Subject to derating depending on the ambient temperature and power supply voltage.
[Use the system so that the total current consumption of each station does not exceed 2 A when power is supplied (except immediately after the power is turned on).]
Ripple Noise500 mVp‑p or less
Allowable Momentary Power Outage DurationPS2: Operation continues after a momentary power outage of 10 ms or less.
Protection GradeIP1X
Protection FunctionExcess Current Protection110 to 160%, drooping characteristics, automatically reset
Excess Voltage Protection27 to 33 V, output cutoff, not automatically reset
External Connection Method· Power supply to dedicated power supply: terminal block, 3 points (M3 screw)
· Power supply to communication part and CC-Link/LT system: dedicated CC-Link/LT connector (4 pins) × 2
Mass0.4 kg
Ambient Temperature0 to 55°C - When Operating, -25 to 70°C - When Saving
Relative Humidity5 to 95% RH (No Condensation) - When Operating / When Saving
Vibration ResistanceUnder Intermittent VibrationFrequency: 10 To 57 HzSingle amplitude: 0.075 mm 10 times in each direction of X, Y and Z (total 80 minutes each)
Frequency: 57 To 150 HzAcceleration: 9.8 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each)
Under Continuous VibrationFrequency: 10 To 57 HzSingle amplitude: 0.035 mm 10 times in each direction of X, Y and Z (total 80 minutes each)
Frequency: 57 To 150 HzAcceleration: 4.9 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each)
Impact Resistance147 m/s2, 3 times in each direction of X, Y and Z
Noise ResistanceAchieved through a noise simulator with a noise voltage of 1,000 Vp‑p, noise width of 1 μs and frequency of 25 to 60 Hz.
Withstand VoltageAC type: 15,000 V AC for 1 min
DC type: 5,000 V AC for 1 min
Insulation ResistanceBetween all external terminals at once and the earth terminal: 10 MΩ at 500 V DC on an insulation resistance meter
Operating AtmosphereThere shall be no corrosion gas or flammable gas and not much conductive dust.
Altitude Of Use2,000 m or lower
Cannot be used in environments pressurized higher than the atmospheric pressure. Doing so may cause failures.
Installation LocationInside the control panel
Overvoltage CategoryII or lower
Indicates the assumed wiring part to which the applicable equipment is connected between the public network and the mechanical system in plant. Category II applies to the equipment to which power is supplied from a fixed facility. The surge withstand voltage for equipment of up to 300 V in rating is 2,500 V.
Pollution Degree2 or lower
Index to indicate the degree of conductive material generation in the use environment.
Pollution degree 2 indicates that only non-conductive contaminants will generate.
However, temporary conduction may still occur in the environment due to accidental condensation.
EarthingD-type earthing (earthing resistance: 100 Ω or less)
Part Number
CL1PSU-2A
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to Ship

-

1 Piece(s) Quote

Loading...

  1. 1
 

Basic Information

Rated Input Voltage AC100V / AC120V / AC200V / AC230V / AC240V Maximum Output Voltage/ Current DC24V· 2A Note CC-Link/LT Dedicated Power Supply (2A) - Compatible Standards: UL/ cUL, CE (EMC), CE (LVD)

Please check the type/dimensions/specifications of the part CL1PSU-2A in the Dedicated CC-Link/LT Power Supply series.