(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Instead, please kindly use other browsers like Google Chrome, Microsoft Edge or Mozilla Firefox.

  • Scheduled Maintenance Notice: This site will be unavailable due to scheduled maintenance from 9:00 24/11/2024 to 7:00 (SGT) 25/11/2024. We apologize for the inconvenience.
  • Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information.

CC-Link/LT Remote I/O (Input) Unit

CC-Link/LT Remote I/O (Input) Unit

A high-speed counter unit for the in-line field network CC-Link.

PDF

CC-Link High-Speed Counter Module Comparison

Item AJ65BT-D62 AJ65BT-D62D AJ65BT-D62D-S1
Pulse Input DC input Differential input Differential input
Preset Input DC input DC input Differential input
Counting Range 0 to 16777215
(24-bit Binary)
0 to 16777215
(24-bit Binary)
0 to 16777215
(24-bit Binary)
Number of Occupied Stations 4 4 4
Station Type Remote device station Remote device station Remote device station

Compatible standard: UL/cUL CE(EMC) KC

CC-Link High-Speed Counter Module Common Specifications

Operating Ambient Temperature 0 to 55°C
Storage Ambient Temperature -20 to 75°C
Operating Ambient Humidity 10 to 90% RH, no condensation
Storage Ambient Humidity 10 to 90% RH, no condensation
Vibration Resistance JIS B 3502, IEC 61131-2 Compatible Under Intermittent Vibration Frequency: 5 to 8.4 Hz, single amplitude: 3.5 mm
Frequency: 8.4 to 150 Hz, constant acceleration: 9.8 m/s2
Sweeps: 10 sweeps in each direction of X, Y and Z
Under Continuous Vibration Frequency: 5 to 8.4 Hz, single amplitude: 1.75 mm
Frequency: 8.4 to 150 Hz, constant acceleration: 4.9 m/s2
Impact Resistance JIS B 3502, IEC 61131-2 compatible
(147 m/s2, 3 times in 3 directions of X, Y and Z)
Operating Atmosphere No corrosive gas
Operating Altitude 0 to 2,000 m
Installation Location Inside the control panel
Overvoltage Category II or lower
Pollution Degree 2 or less
Part Number
AJ65BT-D62
AJ65BT-D62D
AJ65BT-D62D-S1
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipClassification Count input signal level Preset External Input Computing Speed (1 Phase Input) Computing Speed (2 Phase Input) Note

SGD 618.90

1 Piece(s) 20 Day(s) DC inputDC5/12/24 V 2 to 5 mADC5/12/24 V 2 to 5 mAHIGH side: 200kpps/Low side: 10kppsHIGH side: 200kpps/Low side: 7kppsDC Input - Preset DC Input - Compatible Standards: UL/cUL CE (EMC)

SGD 618.90

1 Piece(s) 91 Day(s) Differential InputEIA standard RS-422-A differential type line driver level (equivalent to AM26LS31 (Texas Instruments Japan Limited))DC5/12/24 V 2 to 5 mAHIGH side: 400kpps/Low side: 10kppsHIGH side: 300kpps/Low side: 7kppsDifferential Input - Preset DC Input - Conforming Standards: UL/cUL CE (EMC)

SGD 562.84

1 Piece(s) 90 Day(s) Differential InputEIA standard RS-422-A differential type line driver level (equivalent to AM26LS31 (Texas Instruments Japan Limited))EIA standard RS-422-A differential type line driver level (equivalent to AM26LS31 (Texas Instruments Japan Limited))HIGH side: 400kpps/Low side: 10kppsHIGH side: 300kpps/Low side: 7kppsDifferential Input - Preset Differential Input - Conforming Standards: UL/cUL CE (EMC)

Loading...

  1. 1
 

Basic Information

Number of Channels(ch) 2

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)