(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Instead, please kindly use other browsers like Google Chrome, Microsoft Edge or Mozilla Firefox.

  • Scheduled Maintenance Notice: This site will be unavailable due to scheduled maintenance from 9:00 24/11/2024 to 7:00 (SGT) 25/11/2024. We apologize for the inconvenience.
  • Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information.

SPD for equipment (LT-C35G102W)

SPD for equipment LT-C35G102W

A compact type with a built-in detachment device and deterioration indicator

[Features]
· Includes a built-in detachment device. Includes a deterioration indicator.
· The built-in detachment mechanism prevents the SPD from smoking and/or igniting in cases where the ZnO element deteriorates.
· With function for indicating detachment mechanism operation.
· Compact, enables space-saving.
· Combined type between wires and ground protecting from lightning-induced surges.
· Use of multi‐terminal components helped in making the smallest product in the industry. Same dimensions are available for 200V to 500V.
· Safe lightning surge bearing strength.
· Using maximum discharge current 5kA (8 / 20 μs), it is difficult to break even with a large lightning surge.
· A long service life type that stands up to repeated lightning surges of 1000A500 times.

PDF

Japanese Only

Part Number

Configured Part Number is shown.

LT-C35G102W

 
Part Number
LT-C35G102W
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Direct current discharge starting voltage Voltage when starting operations Number of phases, number of wires

SGD 64.98

1 Piece(s) 4 Day(s) or more -500VY wire connection AC 550 V/△ wire connection 320 V2.0kVBetween line and ground 1000 V ± 20%Line 1100V ± 10%Three-phase three-line

Loading...

  1. 1

Basic Information

Application Power Supply Type Integrated Mounting Method Cord direct removal
Class, category Class II Representative Standard UL / CUL / TUV / CSA Dimension vertical(mm) 33.5
Dimension width(mm) 38 Dimension depth(mm) 28 Nominal Discharge Current (8/20 μs) 2500A
Maximum Discharge Current (8/20 μs) 5000A

Please check the type/dimensions/specifications of the part LT-C35G102W in the SPD for equipment series.

Similar Part Numbers

Part Number
LT-C12G801W
LT-C14G801W
LT-C32G801W
LT-C34G801W
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Direct current discharge starting voltage Voltage when starting operations Number of phases, number of wires

SGD 55.90

1 Piece(s) 4 Day(s) or more 10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Single-phase 2-line

SGD 64.98

1 Piece(s) 4 Day(s) or more -400VLine AC480V/ ground 280V1.8kVBetween line and ground 800V ± 20%Line 940V ± 10%Single-phase 2-line

SGD 55.90

1 Piece(s) 4 Day(s) or more 10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Three-phase three-line

SGD 64.98

1 Piece(s) 4 Day(s) or more -400VY wire connection AC 480 V/△ wire connection 280V1.8kVBetween line and ground 800V ± 20%Line 940V ± 10%Three-phase three-line

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)