SPD for equipment

SPD for equipment

A compact type with a built-in detachment device and deterioration indicator

[Features]
· Includes a built-in detachment device. Includes a deterioration indicator.
· The built-in detachment mechanism prevents the SPD from smoking and/or igniting in cases where the ZnO element deteriorates.
· With function for indicating detachment mechanism operation.
· Compact, enables space-saving.
· Combined type between wires and ground protecting from lightning-induced surges.
· Use of multi‐terminal components helped in making the smallest product in the industry. Same dimensions are available for 200V to 500V.
· Safe lightning surge bearing strength.
· Using maximum discharge current 5kA (8 / 20 μs), it is difficult to break even with a large lightning surge.
· A long service life type that stands up to repeated lightning surges of 1000A500 times.

PDF

Japanese Only

Part Number

Configured Part Number is shown.

 
Part Number
LT-C12G801W
LT-C32G801W
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Direct current discharge starting voltage Voltage when starting operations Number of phases, number of wires

SGD 55.90

1 Piece(s) 4 Day(s) or more 10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Single-phase 2-line

SGD 55.90

1 Piece(s) 4 Day(s) or more 10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Three-phase three-line

Loading...

  1. 1

Basic Information

Application Power Supply Type Integrated Mounting Method Cord direct removal
Class, category Class II Representative Standard UL / CUL / TUV / CSA Dimension vertical(mm) 33.5
Dimension width(mm) 38 Dimension depth(mm) 28 Nominal Discharge Current (8/20 μs) 2500A
Maximum Discharge Current (8/20 μs) 5000A