No-Fuse Breakers, Panelboard Model

No-Fuse Breakers, Panelboard Model

Click this image to zoom it.

Move the mouse over the image to zoom

  • Volume Discount

Over 10,000 units have been selected by valued customers. Space-saving, no-fuse breakers for panelboards

  • IEC
  • JIS
  • PSE Law

● DIN rail mounting is possible.
● The panelboard type is compact, allowing it to be used as a distribution panel.
● The lineup now includes 3A ~ 100A rated current.
● JIS Agreement dimensions are 96 mm height and 60 mm depth.
● Accessory equipment can be easily mounted.
● This CE Marking compliant product has passed certification testing.
● Select from breaking capacity of 5 kA and 10 kA.
● Can also be used with 400V power supply systems.

Specifications

No-Fuse Breakers, Panelboard Model:Related Image

TypeAmpere FrameNumber of PhasesRated Breaking Current
(220 V)
Rated CurrentModel
Panelboard Type
(for distribution panel)
30 AFSingle-phase5kA 3AABS-32FB-3A
5AABS-32FB-5A
10AABS-32FB-10A
15AABS-32FB-15A
20AABS-32FB-20A
30AABS-32FB-30A
50 AF5kA40AABS-52FB-40A
50AABS-52FB-50A
100 AF10kA60AABS-102FB-60A
75AABS-102FB-75A
100AABS-102FB-100A
30 AFThree-phase
5kA3AABS-33FB-3A
5AABS-33FB-5A
10AABS-33FB-10A
15AABS-33FB-15A
20AABS-33FB-20A
30AABS-33FB-30A
50 AF5kA40AABS-53FB-40A
50AABS-53FB-50A
100 AF10kA60AABS-103FB-60A
75AABS-103FB-75A
100AABS-103FB-100A

More Information

Specifications
Ampere Frame30AF50AF100AF
TypePanelboard Type
ModelABS-32FBABS-33FBABS-52FBABS-53FBABS-102FBABS-103FB
RatingPole Number232323
Rated Current (A)3, 5, 10, 15, 20, 3040,5060,75,100
Rated Voltage AC (V)460460460
Rated Voltage DC (V)---
Rated Insulation Voltage (V)500500500
Withstand Voltage (V)250025002500
Rated Impulse Voltage KV666
Rated Breaking Capacity (KA)
KSC8321
IEC60947-2
460 VAC2.52.55
380 VAC2.52.55
220 VAC5510
100/110 VAC5510
Outline Drawing (mm)
No-Fuse Breakers, Panelboard Model:Related Image
a5075507575
b969696
c606060
d808080
Product Weight (kg)0.310.410.310.410.430.6
Overcurrent Tripping SystemFull Electromagnetic TypeFull Electromagnetic TypeFull Electromagnetic Type
Installation ConfigurationScrew and DIN Rail Mounting *1Screw and DIN Rail Mounting *1Screw and DIN Rail Mounting *1
Terminal Block Screw SizeM5M5M8
Tightening Torque2.2 ~ 2.7 N·m2.2 ~ 2.7 N·m5.4 ~ 7.3 N·m
Auxiliary EquipmentAuxiliary Contact AXMountableMountableMountable
Alarm Contact AL
External Operating Handle D (Surface Mounting)Non-MountableNon-MountableNon-Mountable
External Operating Handle E (Extending)
Terminal CoverMountableMountableMountable
Standard AcquiredElectrical Appliance and Material Safety ActAcquiredAcquiredAcquired
IEC60947-2AcquiredAcquiredAcquired
CE MarkingAcquiredAcquiredAcquired
*1: 2 mounting screws are included as standard.
 
No-Fuse Breakers, Panelboard Model:Related Image

Inspection after Shutdown
When a breaker shutdown occurs due to accident current, the fuse may be reused or may need to be replaced depending on the situation.
Magnitude of breaking currentDegree of breaker damageMeasures
Operation within time delay tripping
(Overcurrent within approx. 10 times the rated current)
No abnormality other than exhaust portCan break overcurrent of 6 times the rated current for up to 50 times
(100 A or lower)
Relatively low current value
Shorting Current
No-Fuse Breakers, Panelboard Model:Related Image
Large shorting current close to rated breaking capacity
Carbonization around exhaust port can be observed
No-Fuse Breakers, Panelboard Model:Related Image
Carbonization around handle
Carbonization around exhaust port
Fused metal deposit inside breaker
Can be Reused
No-Fuse Breakers, Panelboard Model:Related Image
Replace with New Parts
∙ Perform insulation withstand voltage test if insulation resistance value does not reach 5 MΩ.
∙ Can be used temporarily if the standard withstand voltage is achieved, but an early replacement is recommended.
∙ Can be used if both insulation resistance and withstand voltage are sufficient, but check temperature increase does not occur for a certain period of time.
∙ Perform an operation test of the leakage breaker using the test button.
Part Number
ABS-32FB-3A
ABS-32FB-5A
ABS-32FB-10A
ABS-32FB-15A
ABS-32FB-20A
ABS-32FB-30A
ABS-33FB-3A
ABS-33FB-5A
ABS-33FB-10A
ABS-33FB-15A
ABS-33FB-20A
ABS-33FB-30A
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipAmpere frame Rated block capacity AC 200 V
(kA)
Number of Poles Rated Current
(A)
Dimension width
(mm)

SGD 32.22

1 Piece(s) 4 Day(s) or more 30AF52350

SGD 32.22

1 Piece(s) Same day 30AF52550

SGD 32.22

1 Piece(s) Same day 30AF521050

SGD 32.22

1 Piece(s) 4 Day(s) or more 30AF521550

SGD 32.22

1 Piece(s) 4 Day(s) or more 30AF522050

SGD 32.22

1 Piece(s) 4 Day(s) or more 30AF523050

SGD 36.13

1 Piece(s)Available 4 Day(s) or more 30AF53375

SGD 36.13

1 Piece(s)Available 4 Day(s) or more 30AF53575

SGD 36.13

1 Piece(s)Available 4 Day(s) or more 30AF531075

SGD 36.13

1 Piece(s)Available 4 Day(s) or more 30AF531575

SGD 36.13

1 Piece(s)Available 4 Day(s) or more 30AF532075

SGD 36.13

1 Piece(s)Available 4 Day(s) or more 30AF533075

Loading...

  1. 1

Drawing

No-Fuse Breakers, Panelboard Model:Related Image

Basic Information

Rated block capacity, voltages except VAC 100/200/400, VDC 250 Present Mounting Method DIN/Screw retention Connection Method Surface type
Representative Standard PSE / CE Dimension height(mm) 96 Dimension depth(mm) 75.5
Conforming blocker type FB Model (For Distribution Board) Other standards IEC / KEMA Rated voltage used(V) 220
Notes Rated breaking capacity is the value at 220 VAC

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)