(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Instead, please kindly use other browsers like Google Chrome, Microsoft Edge or Mozilla Firefox.

  • Scheduled Maintenance Notice: This site will be unavailable due to scheduled maintenance from 9:00 24/11/2024 to 7:00 (SGT) 25/11/2024. We apologize for the inconvenience.
  • Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information.

Noise Filter (Single-Phase, Low-Profile) (Part Numbers)

Noise Filter (Single-Phase, Low-Profile)

Click this image to zoom it.

Move the mouse over the image to zoom

  • Volume Discount

[Applications]A measure to prevent noise intrusion from single-phase power supply lines [Features] · Improved workability with self-lifting screws and opening/closing covers · DIN rail mount type also available

  • UL
  • CSA

· Captive screw and open/close model cover improve workability
· DIN rail mounting models are also in lineup


∙ The noise filter cannot be used between the general-use inverter and motor.
∙ When choosing leakage breakers, select the filter leakage current while paying attention to the noise.

PDF

Part Number

Configured Part Number is shown.

ENF-RSEN-2010D

Specifications

Noise Filter (Single-Phase, Low-Profile):Related Image

ModelCircuit ConfigurationRated CurrentShape
(Mounting Method)
ENF-RSEN-2006Single Phase6AStandard (Direct Mount)
ENF-RSEN-2006DDIN Rail Mountable
ENF-RSEN-201010AStandard (Direct Mount)
ENF-RSEN-2010DDIN Rail Mountable
ENF-RSEN-202020AStandard (Direct Mount)
ENF-RSEN-2020DDIN Rail Mountable
ENF-RSEN-203030AStandard (Direct Mount)
ENF-RSEN-2030DDIN Rail Mountable
ENF-RSEN-205050AStandard (Direct Mount)

More Information

Specifications
ModelStandardENF-RSEN-2006ENF-RSEN-2010ENF-RSEN-2020ENF-RSEN-2030ENF-RSEN-2050
DIN Rail MountableENF-RSEN-2006DENF-RSEN-2010DENF-RSEN-2020DENF-RSEN-2030D-
Manufacturer Part NumberStandardRSEN-2006RSEN-2010RSEN-2020RSEN-2030RSEN-2050
DIN Rail MountableRSEN-2006DRSEN-2010DRSEN-2020DRSEN-2030D-
Circuit ConfigurationSingle Phase
Rated Voltage (AC / DC)250V
Rated Current (AC / DC)6A10A20A30A50A
Withstand Voltage2,500 VAC / 1 Minute Interval at 20°C and 65% RH: Between Line-Earth
Insulation Resistance100 MΩ min. 500 VDC at 20°C, 65% RH: Between Line-Earth
Leakage Current1.0mA max.
Direct Current Resistance110 mΩ max.40 mΩ max.10 mΩ max.6 mΩ max.6 mΩ max.
Attenuation Volume Guarantee Range
25 dB Guarantee
Common Mode0.1 ~ 10MHz0.2 ~ 20MHz0.4 ~ 30MHz2 ~ 30MHz1 ~ 30MHz
Differential Mode0.2 ~ 30MHz0.2 ~ 30MHz0.3 ~ 30MHz0.4 ~ 30MHz0.2 ~ 30MHz
Operation EnvironmentTemperature: -25 ~ +85 °C, 15 ~ 85% RH (No Condensation)
Safety StandardsUL1283, CSA C22.2 No.8, EN60939
MassStandard230g230g230g230g865g
DIN Rail Mountable260g260g260g260g-

Noise Filter (Single-Phase, Low-Profile):Related Image
Noise Filter (Single-Phase, Low-Profile):Related Image
Noise Filter (Single-Phase, Low-Profile):Related Image
Noise Filter (Single-Phase, Low-Profile):Related Image
Noise Filter (Single-Phase, Low-Profile):Related Image
Part Number
ENF-RSEN-2010D
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to Ship

SGD 44.70

1 Piece(s)Available Same day

Loading...

  1. 1

Basic Information

Circuit Configuration Single-phase Rated Current(A) 10 Mounting Method DIN rail
Wiring Method Screw fastening Representative Standard UL / CSA Dimension vertical(mm) 52
Dimension width(mm) 98 Dimension depth(mm) 43.4

Please check the type/dimensions/specifications of the part ENF-RSEN-2010D in the Noise Filter (Single-Phase, Low-Profile) series.

Tech Support